Hardware reference guide
Intrinsically Safe Modules
35013379 02 October 2007 469
Field Wiring Field wiring to the module consists of separate shielded, twisted pair wires. The 
acceptable field wire gauge is AWG 20 to AWG 12. Wiring between the module and 
the intrinsically safe field device should follow intrinsically safe wiring practices, to 
avoid the transfer of unsafe levels of energy to the hazardous area.
Terminal Strip 
Color and Keying 
Assignment
The module’s 140XTS33200 field wiring terminal strip is color-coded blue to identify 
it as an intrinsically safe connector.
The terminal strip is keyed to prevent the wrong connector from being applied to the 
module. The keying assignment is given below.
Module Class  Module Part Number Module Coding  Terminal Strip Coding 
Intrinsically Safe  140DIO33000 CDE  ABF 