Hardware reference guide
I/O Modules
35013379 02 October 2007 565
Linear 
Measuring 
Ranges
The following table shows the linear measuring ranges for the 140AMM09000 
combination Analog module.
4x Registers The following figure shows the 4X registers. 
Data Format Input Under 
Warning
Normal Over 
Warning
16-bit 
Format
+/- 10 V < 768 768 ... 64,768 > 64,768
+/- 5 V, +/- 20 mA < 16,768 16,768 ... 48,768 > 48,768
0 ... 10 V 0 ... 64,000 > 64,000
0 ... 5 V, 0 ... 20 mA 0 ... 32,000 > 32,000
1 ... 5 V, 4 ... 20 mA < 6,400 6,400 ... 32,000 > 32,000
Voltmeter 
Format*
+/- 10 V < -10,000 -10,000 ... 10,000 > 10,000
+/- 5 V < -5,000 -5,000 ... 5,000 > 5,000
0 ... 10 V 0 ... 10,000 > 10,000
0 ... 5 V 0 ... 5,000 > 5,000
1 ... 5 V < 1,000 1,000 ... 5,000 > 5,000
+/- 20mA < -20,000 -20,000 ... 20,000 > 20,000
0 ... 20mA 0 ... 20,000  > 20,000
4 ... 20mA  < 4,000 4000 ... 20,000 >20,000
12-bit 
Format 
+/- 10 V  0 0 ... 4,095 4,095
+/- 5 V, +/- 20 mA  0 0 ... 4,095 4,095
0 ... 10 V 0 ... 4,095 4,095
0 ... 5 V, 0 ... 20 mA 0 ... 4,095 4,095
1 ... 5 V, 4 ... 20 mA  0 0 ... 4,095 4,095
Note: The data format is always 0 ... 4095 decimal (in Modsoft).
Channel 1 output dataRegister 1
Channel 2 output dataRegister 2
4x Registers
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com