Hardware reference guide
Hardware Specifications
66
35013379 02 October 2007
I/O Modules – 
Discrete Out
The following table shows specifications for the Discrete Out modules. 
Type/Part 
Number
Function Points/
Channels
Points 
per Group
Bus Current 
Required
Special 
Features
140DAO84000 24 ... 230 Vac 16  N/A 350 mA 4 A per point, 
isolated
140DAO84010 24 ... 115 Vac 16  N/A 350 mA 4 A per point, 
isolated
140DAO84210 115 ... 230 
Vac
16 4 350 mA 4 A per point, 
group fused
140DAO84220 24 ... 48 Vac 16 4 350 mA 4 A per point, 
group fused
140DAO85300 230 Vac 32 8 1A 1 A per point, 
group fused
140DDO15310 5 Vdc 32 8 350 mA 0.5 A per point, 
group fused
140DDO35300 24 Vdc 32 8 330 mA 0.5 A per point, 
group fused
140DDO35301 24 Vdc 32 8 250 mA 0.5 A per point
140DDO35310 24 Vdc 32 8 330 mA 0.5 A per point, 
group fused
140DDO36400 24 Vdc 96 16 250 mA 0.5 A per point, 
group fused
140DDO84300 10 ... 60 Vdc 16 8 160 mA 2 A per point, 
group fused
140DDO88500 24 ... 125 Vdc 12 6 6 points: 375 
mA 
12 points: 650 
mA
0.5 A per point 
with short circuit 
protection,
Group fused
140DRA84000 N.O. Relay 16 1 1,100 mA 2 A per point
140DRC83000 N.O./N.C. 
Relay
8 1 560 mA 5 A per point
140DVO85300 10 ... 30 Vdc 32 8 500 mA 0.5 A per point, 
verified output, 
group fused
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com