Hardware reference guide
I/O Modules
35013379 02 October 2007 687
Fuse Locations The following figure shows fuse locations for the DDO84300 module. 
Internal 8A fuse time-lag for each group (Part # 042701994 or 
equivalent).For location of fuses, see Fuse Locations, 
p. 687.
External Each group is protected with an 8 A fuse to protect the 
module from catastrophic failure. The group fuse is not 
guaranteed to protect each output switch for all possible 
overload conditions. It is recommended that each point 
be fused with a 2 A fuse: Little Fuse 312-002 or 
equivalent.
Specifications
Possible danger to equipment or personnel.
Turn off power to the module and remove the field wiring terminal strip to gain 
access to fuses.
Failure to follow these instructions can result in injury or equipment damage.
CAUTION
140
DDO 353 00
 vdc out
X
Fuse Locations
Points
1-8
Points
9-16
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123 www.barr-thorp.com