Hardware reference guide
CableFast Cabling
802
35013379 02 October 2007
Note: These are the maximum load current capacities of the 140CFA04000 and 
CFG01600 terminal blocks:
1. When using the 140CFA04000 terminal block, the indicated module outputs are 
limited to 0.5 A per point, 150 Vac maximum and 0.5 A per point, 150 Vdc 
maximum.
2. When using the 140CFG01600 terminal block and either the 140XTS012xx or 
140XTS102XX high power cables, the indicated module output ratings are 2 A 
per point, 150 Vac maximum, and 2 A per point, 150 Vdc maximum.
3. The 140CFA04000 block does not incorporate an isometric barrier and is not 
recommended for use with the 140ATI03000 TC module. Without such a barrier, 
temperature readings may vary up to 2 degrees from one end of the block to the 
other. If the application can tolerate this temperature error, the block (and 
module remote CJC) may be used.