Technical information
4/13
Software
Unity Pro software
Small/Large/Extra Large
Application converters
Unity Pro’s integrated conversion tools can be used to convert PLC applications 
created with ModSoft, ProWorX, Concept and PL7 programming software to Unity 
Pro applications.
Concept/Unity Pro converter (Quantum PLC)
This conversion is performed with a Concept application V2.5 or later (it can also be 
performed in V2.11 or later, but only after an update to V2.5). In order to perform the 
conversion, the application must be exported to an ASCII le in Concept. 
The export le is converted to a Unity Pro source le automatically. This le is then 
analyzed by Unity Pro. At the end of the procedure, a conversion report is generated 
and an output window displays any conversion errors and provides direct access to 
the part of the program to be modied. 
The Concept application converter converts the application to Unity Pro, but does 
not guarantee that it will operate correctly in real time. It is therefore essential to test 
or debug all converted applications.
PL7/Unity Pro converter (Premium PLC and Atrium slot PLC)
This conversion is performed with a PL7 application V4 or later (Premium PLC or 
Atrium slot PLC). In order to perform the conversion, the source le (complete 
application or user function block) must be exported in PL7. 
The conversion procedure is similar to that of the Concept conversion described 
above.
Note: Applications created with Concept, Modsoft and ProWORX can be converted to LL984. 
Please contact our Customer Care Center.
Operating system update utilities
The OS-Loader software is designed for updating operating systems on Premium 
and Quantum platforms. It is supplied with Unity Pro software.
It is used to upgrade Unity processors and modules as well as to upgrade PL7 or 
Concept processors and modules to make them compatible with Unity Pro.
OS-Loader software supports:
b Premium processors
b Quantum processors
b Ethernet communication modules 
b EtherNet/IP communication modules
The operating system updates are performed as follows:
b Uni-Telway RS 485 terminal link for Premium processors
b Modbus or Modbus Plus terminal link for Quantum processors
b Ethernet TCP/IP network for integrated Ethernet port on Premium processors and 
Premium and Quantum Ethernet modules
Note: For Modicon M340 and M580 this service is provided by Unity Loader (see page 4/26).
Online modication of the Quantum conguration
This function, also called Change Conguration On The Fly (CCOTF), is used to modify 
the Quantum conguration online (application in RUN mode):
b Addition or removal of discrete or analog I/O modules
b Modication of conguration parameters of discrete or analog I/O modules 
(already present or newly installed)
The CCOTF function is supported by standalone processors for all three types of I/O 
architecture (local, RIO, DIO) using version 5 of Unity Pro, and for Hot Standby 
processors using version 4.1 or higher of Unity Pro. 
The CCOTF function must rst be validated in the Unity Pro conguration screen. 
A conrmation screen appears when the conguration has been modied online.
Functions (continued)
Conguration screen 
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10










