User guide
Maintenance
54  
840 USE 115 00 Version 1.0
The 
Run
 indicator will flash. The 
Coll
 LED also ma
y
 flash, indicatin
g
 that collisions 
are occurrin
g
 on the Ethernet network. Such collisions are normal.
If a fault has occurred, the normal LEDs ma
y
 be extin
g
uished or other indicators 
ma
y
 li
g
ht. This section will discuss errors reported b
y
 the 
Active, Ready, Coll, 
Link, Kernel, Appl
 and 
Fault 
indicators.
For each t
y
pe of error, tr
y
 the su
gg
ested remedies in the order 
g
iven. If no remed
y
su
gg
ested here overcomes the error, consult 
y
our Schneider Automation customer 
representative.
Certain error codes are recorded in the MSTR block. For instructions on how to 
read and interpret those codes throu
g
h Modsoft, please refer to 
MSTR Function 
Error Codes
 on pa
g
e 28. 
6.1.2 Active LED
If the 
Active 
LED fails to li
g
ht, the module is not communicatin
g
 with the 
backplane.
Troubleshooting 1.
Make sure the Ethernet web embedded server module and the controller are 
installed properl
y
. Verif
y
 that the controller is functionin
g
.
If the controller is not functionin
g
, replace it. If neither the new controller nor the 
Ethernet module will function, replace the backplane.
2.
Make sure that no more than two network option modules -- includin
g
 NOE, 
NOM, NOP and CRP 811 modules -- have been installed in the backplane with 
a 140 CPU 113 or 213; no more than six network option modules with a 140 
CPU 424, 434 or 534.
3.
Check the version of the controller executive. You must have version 1.1 or 
g
reater to support the Ethernet web embedded server module. Earlier versions 
do not reco
g
nize the module.
4.
Replace and return the fault
y
 Ethernet web embedded server module.
6.1.3 Ready LED
If the 
Ready
 LED fails to li
g
ht, the module has failed internal dia
g
nostic tests.
Troubleshooting 1.
Make sure that power has been applied to the backplane.
2.
Replace and return the fault
y
 Ethernet web embedded server module.