6.1.4 Link LED
If the 
Link
 LED fails to li
g
ht, the module is not communicatin
g
 with the Ethernet 
hub.
Troubleshooting 1.
Make sure that the cable has been installed correctl
y
 and the module is 
functionin
g
 properl
y
.
2.
Verif
y
 that the hub is workin
g
 properl
y
.
6.1.5 Kernel LED
If the 
Ready
 LED is on and the 
Kernel
 LED is flashin
g
, the module has detected an 
invalid software ima
g
e. If the 
Ready
 LED is on and the 
Kernel 
LED is shinin
g
steadil
y
, an attempt to download a software ima
g
e has failed and the module is in 
kernel mode.
In either case, download a new software ima
g
e, usin
g
 the procedure on pa
g
e 61.
6.1.6 Fault LED
The 
Fault
 LED will flash briefl
y
 followin
g
 an error as the module attempts to 
recover. The 
Fault
 indicator will remain on onl
y
 when the error lo
g
 is full 
(
the error 
lo
g
 has space for 1023 entries
)
. In that case, the module will be unable to recover. 
Use the ERRLOG utilit
y
 to clear the error lo
g
, as described on pa
g
e 57. 
Figure 26  LED Display When the Error Log is Full