User manual
Transferring Data Using Communication Blocks
33002479 06 07/2008 181
Write CTE
Description A write CTE operation writes the CTE configuration table from the specified data 
(DATABUF) to a specified Ethernet configuration extension table or to a specific slot. 
To program an MBP_MSTR block to perform a write CTE operation, use function 
code 12 (see Operational Function Codes, p. 151).
Network 
Implementation
A write CTE operation can be performed on TCP/IP Ethernet (see TCP/IP Ethernet 
Network Statistics, p. 174) and SY/MAX Ethernet networks.
Control Block 
Usage for TCP/IP 
Ethernet
Register Meaning
CONTROL[1]  12 = write CTE
CONTROL[2]  Indicates the error status
CONTROL[3]  The length setting: a value from 12 to 37.
CONTROL[4] No significance
CONTROL[5] Routing register
Least significant byte = mapping index
Either a value displayed in the byte of the address or is not used.
or
Most significant byte = network adapter module slot
CONTROL[6] 
 ...
CONTROL[9] 
The number shown in the least significant byte in the area 1 through 16 
indicates the slot where the optional module is located.










