User manual
SNMP
33002479 06 07/2008 231
Configuring an NOE with TFE Private MIB
Introduction A MIB, a Management Information Base, is an element used in network 
management. Network management services are based on the need to monitor and 
manage:
z performance
z fault occurrences
z security
Each MIB contains a finite number of objects. Manage your MIB with a management 
station running an SNMP management application. The management application 
uses GETs and SETs to retrieve system information and to set system environment 
variables.
Schneider 
Private MIB
Schneider Electric obtained a Private Enterprise Number (PEN) from the Internet 
Assigned Numbers Authority (IANA). That number represents a subtree in the 
SNMP MIB, a number that is a unique identifier used for Groupe Schneider.
The object identifier for the root of the Groupe Schneider subtree is 
1.3.6.1.4.1.3833 and represents a path to the subtree as follows:
Under the GroupeSchneider private MIB is a Transparent Factory Ethernet (TFE) 
private MIB, Transparent_Factory_Ethernet(1).
iso(1)
org(3)
dod(6)
internet(1)
private(4)
enterprise(1)
GroupeSchneider(3833)
Transparent_Factory_Ethernet(1)