User manual
Hot Standby
310
33002479 06 07/2008
Quantum Hot Standby for Unity Pro
The Hot Standby 
Solution
In the hot standby solution, two identically configured PLC systems are set up to 
control the same application. One PLC, the primary, runs the application and 
updates the other secondary (standby) PLC. The standby maintains awareness of 
the application status but does not perform any control functions. In the event of a 
failure in the primary PLC, the standby PLC takes over the primary PLC responsi-
bilities. When the PLC that has failed becomes operational again, it comes back up 
in the hot standby system as the new secondary PLC.
The NOEs coordinate the swapping of IP addresses. After closing both the client 
and the server connections, each NOE sends a swap UDP message to its peer 
NOE. The sending NOE then waits a specified timeout (500 ms) for the peer swap 
of UDP messages. Either after receiving the messages or after a timeout, the NOE 
changes its IP address.
COMMUNICATION FAILURE
Whenever possible, use of a switch (not a hub) to connect the NOE modules to 
each other or to the network. 
Schneider Electric offers switches. Contact a local sales office for more 
information.
Failure to follow these instructions can result in injury or equipment damage.
UNINTENDED EQUIPMENT OPERATION
Design your application so that unmonitored modules support communication only 
to noncritical parts of the application.
Failure to follow these instructions can result in death, serious injury, or 
equipment damage.
Note: NOEs must communicate with each other in order to swap IP addresses. 
Schneider Electric recommends that you connect the primary and secondary 
NOEs to the same switch because:
z Communication failures between the NOEs increases the time to swap.
z Connecting 2 NOEs to the same switch minimizes the probability of a 
communication failure.
CAUTION
WARNING










