User manual
Installation and Configuration
364
33002479 06 07/2008
I/O Scanning 
Parameters
A description of the I/O scanning parameters used in this example are listed in the 
following table.
Parameter Description Example
IP Address The IP address of the scanned Ethernet slave 
device
192.168.1.100
Unit ID The Unit ID field is used to associate the 
slave address of the device connected to an 
Ethernet/Modbus gateway with the IP 
address of that gateway:
z values: 1 to 255
z default value: 255
When using a bridge, enter the bridge index 
(1 to 255) into this field.
255
Health 
Timeout (ms)
In the Health Timeout (ms) field, you can set 
the maximum interval between two 
responses from a remote device. After this 
time period expires, the received data 
becomes invalid. The health timeout should 
be longer than the repetitive rate. For a 
Quantum NOE Ethernet module, the health 
timeout should also be longer than the CPU 
scan time.
z configure range: 1ms to 50 seconds
z interval: 1ms
200ms
Repetitive 
rate (ms)
In the Repetitive rate (ms) field you can 
associate an IP address with its scanning 
period (increments of 16 ms).
64ms
RD Master/
Slave (read) 
parameters* 
Includes three parameters:
z RD Master Object: address in master PLC 
into which newly read information is 
stored.
z RD slave index: source address index in 
the slave/remote device.
z RD length: number of words being read.
RD Master Object:%mw1
RD slave index: 1
RD length: 10
Master Object NOE 771 01 
reads data from slave 
address 198.168.1.100, 
starting at index 1 and puts 
data into NOE’s address 
starting at%mw1 with a read 
size of 10 words.