Wiring Guidelines
Follow the guidelines below when working with the RF Gateway.
Verify that the power supplying the system is turned OFF before
handling electrical power conductors.
Observe national and local electrical codes.
Isolate the RF Gateway from the Class 1 wiring. Consult your
national and local electrical codes for requirements about
isolating Class 1 wiring and Class 2 wiring terminals.
Prevent wire cuttings and debris from entering the unit.
Megger® Testing Guidelines
Do not Megger® test C-Bus data cabling or terminals. Megger
testing of data cabling or terminals can degrade the performance of
the C-Bus network.
It will not harm the units if electrical power terminals only are Megger
tested. But because units contain electronic components, the
Megger readings will not be correct. To obtain valid readings,
disconnect the power lines from the units.
HAZARD OF EQUIPMENT DAMAGE
Do not Megger® test C-Bus data cabling or terminals as it can
degrade the performance of the C-Bus network.
Failure to follow this instruction will result in damage to the C-
Bus network.