Connection to the C-Bus Network
The C-Bus network is connected to the Clipsal RF Wireless Control
System RF Gateway through two polarity sensitive RJ45 inputs
located on the RF Gateway. Connect the unit to the C-Bus network
with Category 5 unshielded twisted pair C-Bus network cable, and a
wired RJ45 plug. Refer to the "Wiring Connections Key Diagram"
figure, and the "RJ45 Pin Connections" table for wiring and pin
connection information.
NOTE: To clearly distinguish C-Bus from other UTP Cat5 cables, it
is recommended to use a different colored cable, or clearly label the
C-Bus UTP Cat5 cable.
NOTE: The Category 5 unshielded twisted pair C-Bus network cable
and the wired RJ45 plug are provided by the installer.
WARNING
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not connect line voltage to any C-Bus terminal.
Failure to follow this instruction can result in personal injury
or equipment or property damage.
Figure 6: Wiring Connections Key Diagram
KEY:
A. C-Bus positive (+): blue + orange
B. C-Bus negative (-): blue/white + orange/white
C. Remote OFF: brown + brown/white*
D. Remote ON: green + green/white*