70 LNT 710 00 DeviceNet Communication Adapter for Modicon TSX Momentum User Guide 870 USE 104 00 Version 2.
Data, Illustrations, Alterations Data and illustrations are not binding. We reserve the right to alter products in line with our policy of continuous product development. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us by e-mail at techcomm@modicon.com. Training Schneider Electric offers suitable further training on the system. Please find the nearest Schneider Electric sales office by visiting http://www.schneider-electric.com.
Modicon TSX Momentum DeviceNet Communication Adapter 170 LNT 710 00 1 This Communication Adapter can be connected to any TSX Momentum I/O base to create a functional I/O module. It provides direct connection to the DeviceNet network, enabling a programmable controller or other DeviceNet master device to communicate with field devices wired to the I/O base terminals. Figure 1 shows the layout of a typical adapter and I/O base.
DeviceNet Communication Adapter 1.1 Product Overview 1.1.1 Function This adapter is installed on any TSX Momentum I/O base to form a complete I/O module that communicates on a DeviceNet network. A programmable controller or other DeviceNet master device on the network can then read from the input terminals and write to the output terminals of the I/O base.
DeviceNet Communication Adapter 1.2 Specifications Table 1 General Specifications Description ODVA compliance Data rate Network power loading Required enclosure Environment, RFI, EMI Agency approval Table 2 Specification Complies with ODVA Specification Release 2.0 for group 2 only slave supporting polled and strobed connections. Supports 125/250/500 Kbaud standard DeviceNet rates. Voltage: Operational from 11 ... 25 Vdc. Current drain: 110 mA maximum, 75 mA typical.
DeviceNet Communication Adapter 1.2.1 Exec. V. 1.10 vs. V. 1.20 Exec. V. 1.20 changed the behavior of certain I/O bases if a field side fault occurred. This change affects the following bases. H H H H 170 170 170 170 ADM ADM ADM ADM 350 350 390 370 10 11 10 10 The following table describes the differences between the two versions in more detail. Refer to the TSX Momentum I/O Base User Guide (870 USE 002 00) for module specifications. Table 3 Exec. V. 1.10 vs. V. 1.
DeviceNet Communication Adapter 1.3 Status Indicators The adapter has three front panel indicators showing its operating status. Figure 2 Status Indicators Power ON (Green) Pwr DeviceNet MNS IO Module/Network Status (Green/Red) NA X 10 I/O Status (Green/Red) Table 4 Power ON Indicator Indicator State Green (steady) Off Table 5 Status Normal operation: power is present from I/O base. Adapter is not receiving power from I/O base.
DeviceNet Communication Adapter 1.4 Connecting to the Network 1.4.1 Network Connector The adapter has one 5–pin male connector for connection to the network. Its pin–to–pin spacing is 5.00 mm. A suggested mating connector is: Schneider Automation part 170 XTS 060 00. Figure 3 1.4.
DeviceNet Communication Adapter 1.5 Setting the Network Node Address DeviceNet nodes are identified by unique addresses assigned to them by the user, in the range 0 ... 63. Duplicate addresses are not allowed. The address is assigned in a pair of rotary switches on the adapter’s front panel. The address that is set in the switches must correspond to the address defined for that adapter in the application program.
DeviceNet Communication Adapter Figure 5 Setting the Network Node Address Do not install any adapter unless you have set its network address for your application. Pwr DeviceNet MNS IO 170 LNT 710 00 NA X 10 X 1 See your network administrator to get the node address for each adapter. X 10 X 1 This example sets the address to 31. 8 Node Upper Address Switch 0 ... 9 0 10 ... 19 1 20 ... 29 2 30 ... 39 3 40 ... 49 4 50 ... 59 5 60 ... 63 6 Lower Switch 0 ... 9 0 ... 9 0 ... 9 0 ... 9 0 ... 9 0 ...
DeviceNet Communication Adapter 1.6 Electronic Data Sheet (EDS) Disk An Electronic Data Sheet (EDS) disk is included with this guidebook. It supplies the parameters for setup of each type of I/O base. Each file’s format on the disk complies with the ODVA specification for DeviceNet I/O module EDS parameters. README.TXT File The disk contains a README.TXT file in a standard text (ASCII) format, which can be viewed and printed with any standard word processor or text editor program. The README.