- Installing the InsightFacility Security Certificate
26-pin Connector Pinouts
Figure 4 26-pin connector
Bottom Row
2 9–24VDC power input
4 GND
6* 12VDC digital input 1
8* 12VDC digital input 2
10 ISO1 CAN GND
12 ISO1 CAN L
14 ISO1 CANH
16 ISO2 RS485 GND
18 ISO2 RS485 1A
20 ISO2 RS485 1B
22 ISO2 RS485 GND
24 ISO2 RS485 2A
26 ISO2 RS485 2B
1
3 5 7 9 11 13 15 17 19 21 23 25
2
4 6 8 10 12 14 16 18 20 22 24 26
Top Row
1 GND
3* 0–10VDC analog input 1
5* 0–10VDC analog input 2
7 GND
9* 4–20mA input 1
11* 4–20mA input 2
13 GND
15* Relay 1 NO
17* Relay 1 COM
19* Relay 1 NC
21* Relay 2 NO
23* Relay 2 COM
25* Relay 2 NC
* These pins are currently reserved for future functionality, check sesolar.com for updates.