InsightFacility Manual
Table Of Contents
- Safety Information
- Audience
- About
- Overview
- Installation
- Getting Started
- Configuring Devices
- Monitoring
- Troubleshooting
- Specifications
- Installing the InsightFacility Security Certificate
d. If you have two separate Xanbus networks connect the second network to
Xanbus 2.
e. Devices on the Xanbus 1 network will not communicate with devices on the
Xanbus 2 network.
f. See Figure 7 for Xanbus 1 pair of ports - one top and one bottom.
NOTICE
EQUIPMENT DAMAGE
n Do not connect a Xanbus cable plug into the Ethernet port on the InsightFacility.
n Connect only to Xanbus ports and use the network terminators to each end device in
the daisy chain.
n Do not connect Xanbus 1 and Xanbus 2 together as the system will become unstable.
Failure to follow these instructions can result in equipment damage.
Figure 7 Sample Xanbus network
2
1
5
6
6
4
3
Xanbus1 Xanbus2
1 InsightFacility unit
2 Conext XW Pro
3 MPPT 80 600
4 Conext AGS (automatic generator start)
5 Conext SCP (system control panel)
6 Network terminators
NOTE: This Xanbus 1 network is for illustration purpose only.
Installation InsightFacility Owner's Guide
990-91411A 26