Turning On the InsightFacility
Before turning on the InsightFacility, you must connect it to a power source.
Figure 9 Power connections and button
Xanbus
26-pin connector
[A]
[B]
[C]
AC/DC power
adapter
NOTE: In the 26-pin connector, pin 1 connects to a 9-24VDC source and pin 2 connects
to GND Power input. See "26-pin connector" on page18.
To turn on the InsightFacility:
1. Select a power source to the InsightFacility. You can choose either of the following:
a. Plug the (A) AC/DC power adapter into the AC wall outlet
b. Connect the InsightFacility to the Xanbus network (B) using Ethernet cables
WARNING
UNINTENDED OPERATION HAZARD
Xanbus is a valid power source for the InsightFacility, however, if you use
Xanbus for the first time set-up the InsightFacility clock will override the other
Xanbus devices’ clocks and could trigger unintentional time-based events, such
as a generator starting.
Ensure that you set the InsightFacility clock and time zone before performing
any other commissioning steps, refer to Changing the Time on page 42 for
instructions.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
c. Provide 9–24VDC power via by connecting to a power input source via the 26-
pin connector (C)
NOTE: An external power supply is not needed if the InsightFacility is connected to a
Conext XW+ inverter, XW Pro inverter, MPPT-80, or MPPT-100 device.
2. Connect (A), (B), or (C)'s connector to InsightFacility's Power port for (A), Xanbus
port for (B), or terminal block for (C), respectively.
3. Connect (A)'s power plug to an AC wall outlet, connect (B)'s other Xanbus cable
connector to a Xanbus port on a Xanbus device, or connect (C)'s pins 1 & 2 to an
energy-limited DC source (9–24VDC).
InsightFacility Owner's Guide Installation
29 990-91411A