Schneider Electric XW+ PDP Installation Manual

1
975-0735-01-01 Revision B
05-2015
solar.schneider-electric.com
Conext Mini Power Distribution Panel Installation Guide
865-1013-01
Contact Information
Please contact your local Schneider Electric Sales Representative or visit the Schneider Electric website at:
http://solar.schneider-electric.com
B
Important Safety Information
A
Important Safety Infomation
C
Materials List
5 x #6 AWG (13.3 mm²)
cables for AC connections:
L1, L2, Neutral (labelled)
---Pre-wired---
1 x #2 AWG (33.6 mm²)
cable for grounding (labelled)
---Pre-wired---
Mini PDP enclosure with
cabinet door, manual holder,
and removable faceplate
1 x GJ 250A 160 VDC,
3/8" stud DC breaker
3 x 2-pole, 60 Amp 120/240 VAC
breakers (Square D QOU260) and
bypass lever
Factory Installed Components
Installer Provided Tools and Materials:
Torque screwdriver (up to 60 in-lbf)
Torque wrench (up to 150 in-lbf)
Spirit (Carpenter’s) Level
Screws for wall mounting the Mini PDP
(select proper screws for selected
mounting surface)
Connecting Conext MPPT Solar Charge Controllers to the Mini PDP
Additional DC breakers are required for connecting MPPT 60 150 and MPPT 80 600 solar
charge controllers to the Mini PDP. There are two additional breaker positions that are
available for mounting DC and/or PV breakers.
The following DC breakers are recommended for use with the Mini PDP and are available
from Schneider Electric distributors and retailers:
100A, 125VDC Breaker Master Pack (865-1080) for MPPT 80 600 output, battery side
80A, 125 VDC Breaker Master Pack (865-1070) for MPPT 60 150 output, battery side
60A, 160VDC Breaker Master Pack (865-1075) for MPPT 60 150 input, PV array side
This Guide is intended for qualified personnel. Certain configuration tasks should only be performed by qualified
personnel in consultation with your local utility and/or an authorized dealer. Electrical equipment should be installed,
operated, serviced, and maintained only by qualified personnel. Servicing of batteries must only be performed or
supervised by qualified personnel with knowledge of batteries and their required precautions.
Qualified personnel have training, knowledge, and experience in:
Installing electrical equipment
Applying applicable installation codes
Analyzing and reducing the hazards involved in performing electrical work
Installing and configuring batteries
Selecting and using Personal Protective Equipment (PPE)
No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E
or CSA Z462.
This equipment must only be installed and serviced by qualified electrical personnel.
Never operate energized with covers removed
Energized from multiple sources. Before removing covers identify all sources, de-energize, lock-out, and tag-out
and wait 2 minutes for circuits to discharge
Always use a properly rated voltage sensing device to confirm all circuits are de-energized.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Batteries can present a risk of electric shock and high short-circuit current. The following precautions must be
observed when working with batteries:
Remove watches, rings or other metal objects.
Use tools with insulated handles.
Wear protective glasses, gloves and boots.
Do not lay tools or other metal parts on top of batteries.
Disconnect the charging source prior to connecting or disconnecting battery terminals.
Failure to follow these instructions will result in death or serious injury.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Battery Circuit Breakers must be installed according to the specifications and requirements specified by
Schneider Electric.
Servicing of batteries must only be performed by qualified personnel and the required precautions. Keep
unqualified personnel away from batteries.
Failure to follow these instructions will result in death or serious injury.
1. The Mini PDP is compatible with the Conext XW/XW+ inverter/charger only.
2. Before installing the Mini PDP and using it with the inverter, read all instructions and cautionary markings on the
unit, the batteries, and all appropriate sections of this manual.
3. Use of accessories not recommended or sold by the manufacturer may result in a risk of fire, electric shock, or
injury to persons.
4. The Mini PDP and inverter are designed to be permanently connected to your AC and DC electrical systems. The
manufacturer recommends that all wiring be done by a certified technician or electrician to ensure adherence to
the local and national electrical codes applicable in your jurisdiction.
5. To avoid a risk of fire and electric shock, make sure that existing wiring is in good condition and that wire is not
undersized. Do not operate the inverter with damaged or substandard wiring.
6. Do not operate the inverter with the Mini PDP if it has been damaged in any way.
7. The inverter does not have any user-serviceable parts. Do not disassemble the inverter except where noted for
connecting wiring and cabling. See your warranty for instructions on obtaining service. Attempting to service the
unit yourself may result in a risk of electrical shock or fire. Internal capacitors remain charged after all power is
disconnected.
8. To reduce the risk of electrical shock, disconnect both AC and DC power from the inverter before attempting any
maintenance or cleaning or working on any components connected to the inverter. Putting the unit in Standby
mode will not reduce this risk.
9. The inverter must be provided with an equipment-grounding conductor connected to the AC input ground.
10. Do not expose the Mini PDP and the inverter to rain, snow, or liquids of any type. These products are designed
for indoor use only. Damp environments will significantly shorten the life of this product and corrosion caused by
dampness will not be covered by the product warranty.
11. To reduce the chance of short-circuits, always use insulated tools when installing or working with this equipment.
12. Remove personal metal items such as rings, bracelets, necklaces, and watches when working with electrical
equipment.
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
DANGER
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
WARNING
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
CAUTION
NOTICE is used to address practices not related to physical injury.. The safety alert symbol shall not be used with
this signal word.
NOTICE
Save These Instructions
This guide contains important safety instructions for the Conext Mini PDP for the XW/XW+ Inverter/Charger that must
be followed during installation procedures. Read and keep this Installation Guide for future reference.
Read these instructions carefully and look at the equipment to become familiar with the device before trying to install,
operate, service or maintain it. The following special messages may appear throughout this bulletin or on the
equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of either symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists
which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety
messages that follow this symbol to avoid possible injury or death.
The Conext XW/XW+ Mini PDP may not be available in all regions; installation is dependent upon your local
electrical code. Consult your local electrical authority to ensure your installation is code-compliant.
NOTICE
Exclusion for Documentation
UNLESS SPECIFICALLY AGREED TO IN WRITING, SELLER
(A) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION
PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION;
(
B) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS, OR EXPENSES, WHETHER SPECIAL, DIRECT,
INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF
ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USERS RISK, AND
(C) REMINDS YOU THAT IF THIS MANUAL IS IN ANY LANGUAGE OTHER THAN ENGLISH, ALTHOUGH STEPS HAVE BEEN TAKEN TO
MAINTAIN THE ACCURACY OF THE TRANSLATION, THE ACCURACY CANNOT BE GUARANTEED, APPROVED CONTENT IS
CONTAINED WITH THE ENGLISH LANGUAGE VERSION WHICH IS POSTED AT WWW.SCHNEIDER-ELECTRIC.COM.
Mini Power Distribution Panel (Mini PDP) and parts for
connecting to the Conext XW/XW+ inverter/charger
XW+ unit (not included)
Other hardware:
3 x plastic bushings for AC
knockouts between XW/XW+
and the mini PDP
2 x wire lugs (spare)
4 x hex head bolts
(3/8-16 x 3/4")
4 x split washers (3/8")
4 x flat washers (3/8")
5 x plastic
cable ties
Label sheet