Instruction Manual

Table Of Contents
Configuring Battery Characteristics and Battery Charging
975-0400-01-01 Revision H 3–7
This manual is for use by qualified personnel only.


12V: 10.0–
13.5V
24V: 20.0–
27.0V
36V: 30.0–
40.5V
48V: 40.0–
54.0V
60V: 50.0–
67.5V
12.5V
25.0V
37.5V
50.0V
62.5V
Sets the voltage at which the
charger transitions from Float
or No Float back to Bulk, or
from Absorption back to Bulk.


120–360 min 180 min Sets the maximum time spent
at a constant voltage (the
setting for Absorption
voltage) during the
absorption stage. This setting
does not control the duration
of the entire Absorption
stage.


Bulk, Float, No
Float
Bulk Manually sets the charge
stage to bulk, float, or no
float.


Cold, Warm,
Hot
Warm Sets the default battery
temperature for
compensation when the BTS
is not connected. Cold is
suitable for temperatures of
around 10 °C (50 °F), Warm
for 25 °C (77 °F), and Hot for
40 °C (104 °F). This screen
appears only when a BTS is
not connected.


-40–65 C n/a Shows the battery
temperature (in Celsius)
detected by the BTS. This
screen appears only when a
BTS is connected.


3 Stage,
2 Stage No
Float
3 Stage Selects the charging cycle
(or algorithm)—3 Stage (Bulk/
Absorption/Float) or 2 Stage
(Bulk/Absorption/No Float).
Table 3 - 2 Battery Menu Values
Setting Values Default Description