Configuring Battery Characteristics and Battery Charging
975-0400-01-01 Revision H 3–7
This manual is for use by qualified personnel only.
12V: 10.0–
13.5V
24V: 20.0–
27.0V
36V: 30.0–
40.5V
48V: 40.0–
54.0V
60V: 50.0–
67.5V
12.5V
25.0V
37.5V
50.0V
62.5V
Sets the voltage at which the
charger transitions from Float
or No Float back to Bulk, or
from Absorption back to Bulk.
120–360 min 180 min Sets the maximum time spent
at a constant voltage (the
setting for Absorption
voltage) during the
absorption stage. This setting
does not control the duration
of the entire Absorption
stage.
Bulk, Float, No
Float
Bulk Manually sets the charge
stage to bulk, float, or no
float.
Cold, Warm,
Hot
Warm Sets the default battery
temperature for
compensation when the BTS
is not connected. Cold is
suitable for temperatures of
around 10 °C (50 °F), Warm
for 25 °C (77 °F), and Hot for
40 °C (104 °F). This screen
appears only when a BTS is
not connected.
-40–65 C n/a Shows the battery
temperature (in Celsius)
detected by the BTS. This
screen appears only when a
BTS is connected.
3 Stage,
2 Stage No
Float
3 Stage Selects the charging cycle
(or algorithm)—3 Stage (Bulk/
Absorption/Float) or 2 Stage
(Bulk/Absorption/No Float).
Table 3 - 2 Battery Menu Values
Setting Values Default Description