Instruction Manual

Table Of Contents
Configuration
3–12 975-0400-01-01 Revision H
This manual is for use by qualified personnel only.
Configuring Charge Controller Input
On the Input Menu you can disable automatic maximum power point tracking
and configure the reference voltage level at which the solar charge controller will
operate the array. Configuring the reference voltage is not required for normal
operation, but can be useful for non-PV applications or for testing purposes.
The Input Menu is an advanced menu item. To display the Input Menu, go to the
Display Menu, view the Display Mode screen and select Advanced. See
“Configuring the LCD” on page 3–17.
Figure 3-4 Input Menu
Table 3 - 4 Input Menu Values
Setting Values Default Description


Auto,
Manual
0.0–150.0V
Auto, n/a Line 1: Enables (Auto) or
disables (Manual) MPPT.
Line 2: When tracking is set to
Manual, you can select the
reference voltage at which
solar charge controller
operates the array. When
tracking is set to Auto, the
reference voltage updates to
reflect tracking activity.


0–200 n/a Records the maximum input
voltage from the array during
the lifetime of the solar charge
controller. You cannot reset
this screen.

SolarArray
1–16
SolarArray
1
Sets the input connection for
the solar charge controller.


 
Advanced menu
=
Enter Exit



