Configuration
3–14 975-0400-01-01 Revision H
This manual is for use by qualified personnel only.
Low Batt
Voltage,
Hi Batt Voltage,
Hi Array
Voltage,
Low Batt Temp,
Hi Batt Temp, Hi
Heat Sink
Temp, Fault
Low Batt
Voltage
Selects the desired condition
to activate the Aux Output.
Depends on Trigger
Source (see Table 3-6)
Line 1: Selects the battery or
array voltage to activate Aux
Output. If the selected Trigger
Source is Hi Batt Temp, Low
Batt Temp, or Hi Heat Sink
Temp, this screen displays
Trigger Temperature Level in
degrees Celsius.
Line 2: Selects the battery or
array voltage to turn off the
Aux Output. If the selected
Trigger Source is Hi Batt
Temp, Low Batt Temp, or Hi
Heat Sink Temp, this screen
displays Clear Temperature
Level in degrees Celsius.
This screen is hidden if the
trigger source is set to Fault.
00:00–09:59
(mm:ss format)
00:00 Line 1: Selects how long the
selected trigger source must
be active before the Aux
Output activates. This can
avoid unnecessary triggering
by momentary loads.
Line 2: Selects how long the
trigger condition must remain
inactive before the Aux
Output turns off.
This screen is hidden if the
trigger source is set to Fault.
5V–13V 12V Selects the active high
auxiliary output voltage (the
active low output voltage is
0V).
Table 3 - 5 Aux Menu Values
Setting Values Default Description