Configuration
3–20 975-0400-01-01 Revision H
This manual is for use by qualified personnel only.
Table 3 - 8 Device Menu Values
Setting Values Default Description
Operating,
Standby,
Hibernate
Operating Operating is the normal mode
for the unit.
Standby disables the output by
disconnecting the main power
circuit from the battery. The unit
cannot charge. The unit still
draws some power from the
battery to operate. The LCD
stays on.
Hibernate performs the same
actions as Standby, but it also
disables all Xanbus network
communications.
n/a n/a Xanbus system ID.
00 to 31 00 Displays the device number for
the solar charge controller. This
number is selected when the
solar charge controller is first
powered up, and uniquely
identifies devices of the same
type (Charge Controllers,
Inverter/Chargers, control
panels, and so on) in a
networked installation.
n/a n/a Firmware version and firmware
build number. This screen is
identical to the screen shown at
startup.
All
available
device
numbers.
01 Enables one-step configuration
of a new solar charge controller
in a multi-unit installation. Select
the device number of the unit
you wish to copy the setup
from. This screen is hidden
when no compatible devices
are found.
The “Copy Setup From?”
command copies all Battery
Menu settings and Custom
Battery Menu settings from the
selected unit.