Installation Guide

The charge controller’s
On/Charging (green)
LED is flashing.
The charge controller is outputting charge
current.
No problem. This is intended operation. See
“Viewing Status Information on the Solar Charge
Controller” in the Conext MPPT 80 and MPPT 100
Owner's Guide for LED status information.
Replacing the Ground Fault Protection Fuse
DANGER
HAZARD OF ELECTRIC SHOCK
If a ground fault is indicated, normally grounded PV conductors could be ungrounded and
energized. Before working on any portion of the array or wiring, make sure that portion of
the array is de-energized by blanketing, use of disconnects, or other safe working
procedures and by testing for voltage before beginning work.
Failure to follow these instructions will result in death or serious injury.
The ground fault protection fuse blows when a significant leakage current flows between
the PV array and earth ground or when the system has been installed with deficient
wiring. Before replacing the fuse, it is important to have qualified service personnel, such
as a certified electrician or technician, determine the cause of the ground fault and effect
repair.
To replace the ground fault protection fuse:
1. Make sure the PV and battery disconnect switches are open and the charge controller
is de-energized.
2. Remove the wiring compartment cover, as described in Wiring on page 31. The
ground fault protection fuse is located behind the wiring terminals.
3. Remove the blown fuse and replace it with a new AC/DC midget cartridge, DC-rated
600 VDC, 1 A (Littelfuse® KLKD 1 or equivalent). Be careful not to damage the fuse
clips, circuit board, and surrounding components.
4. Replace the wiring compartment cover.
5. Clear the fault and reset the system by removing and then reapplying both PV and
battery power.
Ground Faults in a Normally Ungrounded Array
DANGER
HAZARD OF ELECTRIC SHOCK
If a ground fault is indicated, normally grounded PV conductors could be ungrounded and
energized. Before working on any portion of the array or wiring, make sure that portion of
the array is de-energized by blanketing, use of disconnects, or other safe working
procedures and by testing for voltage before beginning work.
Failure to follow these instructions will result in death or serious injury.
Conext MPPT 80 and MPPT 100 Installation Guide Troubleshooting
53 This document is for use by qualified personnel 990-91319