Default Battery Charging Settings
All settings in the following table are based on a 48 V nominal battery bank at 25°C
(7F). For a 24 V nominal battery bank, divide the voltage values in this table by two.
Setting
Battery Type
Flooded
1
Gel AGM
Equalize Voltage 64.0 V n/a n/a
ReCharge Voltage 50.0 V 50.0 V 50.0 V
Bulk Voltage 57.6 V 56.8 V 57.2 V
Absorption Voltage 57.6 V 56.8 V 57.2 V
Float Voltage 54.0 V 55.2 V 53.6 V
Absorption Time 180 min 180 min 180 min
Batt Temp Comp -108 mV/C -108 mV/C -84 mV/C
1
When Custom is selected for the battery type, the default settings are based on the flooded
battery type.