Owner's Guide

Table Of Contents
Advanced
Settings >
Charger
Settings
Batt
Voltage
24V
48V
48V
Sets your nominal battery voltage. Select the nominal voltage level
that matches your system’s battery voltage.
Changing the battery voltage will reset Trigger Level and
Clear Level to their default values for the auxiliary output if
Trig Src is set to LowBattV or HighBattV (see Table 4 on
page 36).
Advanced
Settings >
Charger
Settings
Batt Type
Flooded GEL
AGM
Custom
Flooded
Sets your battery type. Selecting Custom allows you to adjust
equalize, bulk, absorption, and float voltage settings (these settings
will be referred to 2C (77°F) battery temperature). You can also
adjust battery temperature compensation from the Custom
Battery menu. The Customoption is available only when
advanced menus are displayed.
Advanced
Settings >
Charger
Settings
Batt
Capacity
0–10000Ah 440Ah
Sets the amp-hour capacity of your battery bank.
Setting Batt Capacity to 0 disables the exit current threshold
mechanism used to transition from absorption to float. As a result, the
charge controller will transition to float once the Max Absorption
timer has elapsed.
Advanced
Settings >
Charger
Settings
Max Chg
Rate
1–100% 100%
Sets the charging current limit as a % of the charge controller's
nominal capacity (100A for Conext MPPT 100 600 or 80A for Conext
MPPT 80 600).
Advanced
Settings >
Charger
Settings
ReCharge
Volts
24V: 20.0–
30.0V
48V: 40.0–
60.0V
25.0V
50.0V
Sets the voltage at which the charger transitions from float or no float
back to bulk or from absorption back to bulk.
Advanced
Settings >
Charger
Settings
Absorb
Time
1–480min 180min Sets the maximum time spent in the absorption stage.
Setup Force Chg
Bulk Float
No Float
Bulk Manually advances the charge stage to bulk, float, or no float.
Advanced
Settings >
Charger
Settings
Default
Batt Temp
Cold Warm Hot Warm
Sets the default battery temperature for compensation when a BTS is
not connected. Coldis suitable for temperatures around 10°C
(50°F), Warmfor 25°C (7F), and Hotfor 4C (104°F). Battery
charging voltages are set for 2C (77°F) (Warm) and will be
compensated when the battery temperature differs from this value.
This screen appears only when a BTS is not connected.
Setup >
Meters
Batt Temp -4065 C n/a
Shows the battery temperature (in Celsius) detected by the BTS. This
screen appears only when a BTS is connected.
Configuration Conext MPPT 80 and Conext MPPT 100 Owner’s Guide