Viewing Status Information on the Conext System Control Panel or
Conext Gateway
Conext System Control Panel
Use the Conext System Control Panel (SCP) to configure, view system information and
operating status. See Conext System Control Panel Menus on page 73 for an overview
of the SCP, or see the SCP Owner’s Guide (Document Part Number 975-0298-01-01).
n When in Charge Control mode the SCP displays parameters such as PV
voltage, battery voltage, and charge current on the XW MPPT80 or XW
MPPT100 Home screen.
n When a fault or error condition exists, the SCP Fault/Warning light is solid, and
the SCP shows Fault Active on the XW MPPT80 or XW MPPT100 Home
screen.
n When a warning condition exists, the SCP Fault/Warning light is flashing, and
the SCP shows Warning Active on the XW MPPT80 or XW MPPT100
Home screen.
Normal Operation
From the XW MPPT80 Setup or XW MPPT100 Setup screen, select Meters to view
normal operation information. This information is refreshed once per second.
Display Description
PV In Power Measured input power.
PV In Measured input voltage and current.
DC Out Power Power being produced by the charge controller now.
DC Out Measured output voltage and output current.
Time in Float
00:00:00
Elapsed time that the charge controller has been in float in hh:mm:ss format.
Today Accumulated amp hours and kilowatt hours produced today by the charge controller.
Life Lifetime accumulated amp hours and kilowatt hours produced by the charge controller.
Batt Temp Battery temperature detected by the BTS. If a BTS is not connected, then no value is shown.
Display Description
State Charge stage. SeeTable 13
Aux Auxiliary output state. See Table 4 on page 36
Thermal Derating
Indicates whether the charge controller is derating output power due to high operating temperatures. See
Figure 12 on page 69
Table 12Normal operation information (Meters screen)
Operation Conext MPPT 80 and Conext MPPT 100 Owner’s Guide
990-6214B This document is for use by qualified personnel 45