Configuring the Unit
WARNING
RISK OF FIRE AND ELECTRIC SHOCK
The Advanced settings for devices other than the SCP are intended for qualified
installation/service personnel only. Before changing advanced settings, you must be
familiar with the settings and the system-wide impact of changing those settings. Setting
parameters incorrectly could damage connected equipment (such as batteries) or could
severely affect the performance of your system. Incorrect charging configuration can lead to
battery damage and risk of fire. Consult the local utility before enabling sell mode or
changing sell mode settings.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
The charge controller can be configured using the following devices:
n Conext System Control Panel (SCP)
n Conext Gateway
Conext System Control Panel (SCP)
Figure 5Conext SCP
Standby
Event/Warning
Conext XW SCP
For configuration information, see Conext System Control Panel Menus on page 73, or
the SCP Owner’s Guide (Document Part Number 975-0298-01-01).
See the following sections in the SCPOwner's guide to configure the Conext MPPT 80
or MPPT 100:
n Putting the charge controller into Standby mode (see "System Modes" in the
SCPOwner's guide)
Important:Any configuration (change in settings) made when the Solar Charge
Controller is in Operating mode will not be saved unless the charge controller is put
into Standby and then back to Operating mode. These modes can be set using the
System Settings menu in the SCP. Always put the charge controller into Standby
Conext MPPT 80 and Conext MPPT 100 Owner’s Guide Configuration
29 This document is for use by qualified personnel 990-6214