n Cold: 10°C (5F)
n Warm: 25°C (77°F)
n Hot: 40°C (104°F)
If significant seasonal variations are common in your area, change the settings multiple
times during the year for optimal battery charging.
Configuring Peak Power Tracking
You can disable automatic maximum power point tracking and fix the reference voltage
level at which the charge controller operates the array. Fixing the array operating
reference voltage is not required for normal operation, but it can be useful for testing
purposes.
SCP Device
Menu Item
Setting Values Default Description
Advanced
Settings > Input
Settings
MPPT
AutoTrack
Disabled
Enabled
Enabled Enables or disables MPPT.
Advanced
Settings > Input
Settings
MPPT Ref
Volts
195–600V N/A
When tracking is set to Disabled, you can select the reference
voltage from which the charge controller operates. When tracking
is set to Enabled, the reference voltage updates to reflect
tracking activity.
Advanced
Settings > Multi
Unit Config >
Connections
PV In
SolarArray
1–16
SolarArray1 Sets the input connection for the charge controller.
Table 3Peak power tracking settings
Configuring the Auxiliary Output
Use the Aux Settings menu item to enable and configure the auxiliary output. You can
use the auxiliary output to operate a relay, indicator light, vent fan, alarm, or any other
required function. See Auxiliary Output Functions on page 27. For configurable trigger
sources, you can define trigger level, trigger delay, clear level, and clear delay settings.
Non-configurable trigger sources include errors, warnings, and faults.
To display the Aux menu auxiliary settings, select Advanced Settings > Aux Settings.
Setting Values Default Description
Manual
Aux
ManualOff
ManualOn
Automatic
ManualOff
Sets the operating mode for the auxiliary output. When set to Automatic, the auxiliary
output will operate according to the selected trigger source. You can toggle the auxiliary
relay between NC and NO at any time by selecting ManualOn or ManualOff.
Table 4Aux menu settings
Note: The remaining settings in this table are only visible when Manual Aux is set to
Automatic.
Configuration Conext MPPT 80 and Conext MPPT 100 Owner’s Guide