To manually stop battery equalization:
n On the Setup Menu, scroll to Equalize, and then press Enter.
n Change the setting to Disabled.
Equalization stops, and the charge controller goes to either the float or no float stage,
depending on the charge mode selected.
Remote Power Off (RPO)
It is possible to immediately stop the operation of the charge controller by adding a
remote power off (RPO) switch via the Conext XW+ or Conext XW Pro
Inverter/Charger’s AUX port.
When activated, Xanbus devices such as the Conext XW+ or Conext XW Pro
Inverter/Charger and the charge controller will stop all operation, including solar charging,
effectively transitioning the power system into a standby mode.
For information on the different modes, see Configuring Device Settings on page 40.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
n Do not attempt to service, maintain, or troubleshoot the Solar Charge Controller after
activating an RPO switch.
n Disconnect PV conductors before servicing. PV conductors are to be treated as
Hazardous Live and must be disconnected.
n Normally GROUNDED conductors may be UNGROUNDED and ENERGIZED when a
GROUND FAULT is indicated on the front panel. Must be serviced by qualified
personnel.
Failure to follow these instructions will result in death or serious injury.
Operation Conext MPPT 80 and Conext MPPT 100 Owner’s Guide
990-6214 This document is for use by qualified personnel 57