Schneider Electric AGS User Manual

Installation
2–8 975-0307-01-01 Rev G
Important:
The pin number labels in Figure 2-6 are used to designate
the individual wires in the AGS wiring harness for the purpose of this
guide. The number labels are different from the Molex numbers that are
physically marked on the male plug.
Tab le 2- 4 Contact Pin Numbers and Functions
Pin Function
Wiring
Harness Wire
Color
1 Thermostat 1 input Yellow
2 Thermostat 1 return Gray
3 Thermostat 2 input Orange
4 Thermostat 2 return Gray
5 External shutdown input White/Black
6 External shutdown return Gray
7 External manual on input White/Green
8 External manual off input White/Red
9 External ON/OFF LED Indicator output White/Blue
10 Constant 12/24 V B+ (battery positive) for
External ON/OFF/LED Indicator
Red
11 External ON/OFF/LED Indicator return
(connected internally to wire number 13)
Black
12
Generator run signal (switched B+) sense
input
Violet
13
Generator run signal (switched B+) sense
return
Black
14
Relay 1 (Generator run/stop) Normally open
contact
Blue
15
Relay 1 (Generator run/stop) Normally closed
contact
White/Violet
16
Relay 1 (Generator run/stop) Common contact
Gray
17
Relay 2 (Generator start) Normally open
contact
White
18
Relay 2 (Generator start) Common contact
Gray
19
Relay 3 (Preheat/cooldown) Normally open
contact
Brown
20
Relay 3 (Preheat/cooldown) Common contact
Gray
975-0307-01-01_RevG(AGS-Owners).book Page 8 Thursday, August 27, 2015 2:01 PM