Schneider Electric AGS User Manual

Installing the AGS
975-0307-01-01 Rev G 2–9
Connecting the Generator
To connect the Conext AGS to a generator, identify the start wiring
configuration of the generator to be used. Generators must be auto-start
capable, and generators equipped with remote operation connections
are ideal.
If the generator is equipped for remote operation, examine the wiring of
the remote cable and connector (or read the generator’s documentation,
if available) and identify the following wires:
•Ground
•Start
•Stop
Generator run signal, also known as the Hour Meter or Switched B+
(battery positive)
Wiring
Requirements
Either #16 or #18 AWG (1.5mm
2
or 1.0 mm
2
)
wire is required to connect
to the wiring harness. How many of these wires you connect and in which
combination depends on your generator type.
NOTICE
EQUIPMENT DAMAGE
Before connecting the Conext AGS to your generator, read the
Generator Type descriptions in this section and consult your generator
manufacturer to ensure that Gen Type settings and connections are
compatible with your generator.
Damage to the generator can result from selecting an incorrect Gen
Type and following the connection diagram for an incorrect Gen Type
when connecting the Conext AGS to the generator.
Failure to follow these instructions can result in equipment
damage.