Schneider Electric AGS User Manual

Installation
2–10 975-0307-01-01 Rev G
Generator
Type s
The Conext AGS has 14 preset generator configurations, or “Gen Types”
(see “Gen Type” on page 3–12). After installing the hardware, it will be
necessary to select one of these Gen Types from the Conext AGS
Configuration Menu on the SCP.
The following section describes the preset generator configurations and
provides diagrams for connecting the wiring harness to the generator’s
start wiring.
For an explanation of the terminology used in the following section, refer
to Appendix B, “Generator Auto Start Requirements and Types”. For
more information about Conext AGS internal relay activity and timing, see
Appendix C, “Relay Timing”.
B+ Generator
Run Signal
Important: To change the Gen Type, the AGS must first be put in
Standby. See “Placing the Conext AGS in Standby Mode” on page 4–6.
Important: Connecting the B+ Gen Run signal is optional because the
AGS also checks whether AC is present at the AC Input of the inverter via
the Xanbus network. If the B+ Gen Run signal is not connected, it may be
necessary to adjust the Gen Run Signal hold time parameter on the AGS
to a longer time. See “Gen Run Hold Time” on page 3–30.
975-0307-01-01_RevG(AGS-Owners).book Page 10 Thursday, August 27, 2015 2:01 PM