Conext SW 4024-120 Install Guide
Table Of Contents
- Conext™ SW Inverter/Charger
- Exclusion for Documentation
- Document Number: 975-0639-01-03 Revision: Date: 5-2020
- Contact Information solar.schneider-electric.com
- Information About Your System
- About This Guide
- Important Safety Instructions
- Safety Information
- Precautions When Working With Batteries
- FCC Information to the User
- Installation
- Materials List
- Conext SW Front and Side Panels
- Conext SW Supplied Accessories
- Conext SW Required Accessory
- Installation Information
- Before You Begin the Installation
- Installation Codes
- Xanbus Network System
- Xanbus System
- Xanbus-enabled Products and Other Accessories
- Installation Planning
- Planning Preparations
- Components of the Inverter Power System
- Unpacking and Inspecting the Conext SW Inverter/Charger
- Installation Tools and Materials
- Inverter/Charger Installation
- Overview
- Step 1: Choosing a Location for the Inverter/Charger
- Step 2: Mounting the Inverter/Charger
- Step 3: Connecting the AC Input and AC Output Wires
- AC System Bonding
- Step 4: Installing the DC Switchgear and Connecting the DC Cables
- Step 5: Connecting the BTS and Xanbus-enabled Components
- Step 6: Performing Checks Prior to Initial Start-Up
- Step 7: Testing Your Installation
- Battery Information
- Battery Bank Sizing
- Estimating Battery Requirements
- Restrictions on Motor Size
- Battery Cabling and Hook-up Configurations
- Specifications
- Inverter Specifications
- Charger Specifications
- AC Transfer Specifications
- Physical Specifications
- Environmental Specifications
- Regulatory
- Wiring Diagrams
- Single-Inverter System (Off-Grid/Power Backup)
- Single-Inverter System Renewable Energy (Solar)
Specifications
2–2 975-0639-01-03
This guide for use by qualified personnel only
Inverter Specifications
NOTE: All inverter specifications are at nominal conditions: ambient temperature
of 77 °F (25 °C), 24 VDC, unless otherwise specified.
AC Output
SW 2524 120/240 SW 4024 120/240 SW 4048 120/240
Output waveform true sine wave true sine wave true sine wave
Continuous output power (AC)
- Maximum
- 30 minutes
3000 W
a
3300 W
b
a.Only when NoLoadVD is enabled.
b.Duty cycle 3300 W for 30 minutes, 0 W for 45 minutes, NoLoadVD is enabled.
3400 W
4000 W
c
c.Duty cycle 4000 W for 30 minutes, 0 W for 45 minutes.
3800 W
a
4400 W
a
Maximum load power on a
single phase (L1/N or L2/N)
1800 W 2550 W 2700 W
Maximum continuous output
current
12.5 A 15 A 15.2 A
Surge power rating (5
seconds)
5000 W
d
d.Duty cycle 5000 W for 5 seconds, 3000 W for 300 seconds.
7000 W
e
e.Duty cycle 7000 W for 5 seconds, 3400 W for 300 seconds.
7000 W
Inverter peak output current 24 A 41 A 41 A
AC OUTPUT connection Split-phase
(L1/L2)
Split-phase
(L1/L2)
Split-phase
(L1/L2)
Peak efficiency 91.5% 92% 94%
Output power factor
(capacitive or inductive)
0.5 - 1.0 0.6 - 1.0 0.6 - 1.0
Operating voltage range
single-phase/split-phase
104/208 VAC
to 127/
254 VAC
104/208 VAC
to 127/
254 VAC
104/208 VAC
to 127/
254 VAC
Nominal voltage
single-phase/split-phase
120/240 VAC 120/240 VAC 120/240 VAC
Operating frequency range selectable
50 or 60 Hz
selectable
50 or 60 Hz
selectable
50 or 60 Hz
Default output frequency 60 Hz 60 Hz 60 Hz
DC Input
SW 2524 120/240 SW 4024 120/240 SW 4048 120/240
Voltage range 22–34 VDC 20–32 VDC 40–64 VDC
Maximum continuous power
voltage range
22–27 VDC 22–28 VDC 46–48 VDC
Maximum battery current 150 A 230 A 110 A