Conext SW 4048-120 Manual Addendum

Documentation Update
976-0315-01-01 Rev E 13
New Advanced Inverter Settings
PLSDelay
Delays load shaving and AC
support features until the MPPT
has charged the battery in float
mode for 2 hours. See “Grid-
Interactive Delay Feature” on
page 6.
Disabled Disabled,
Enabled
NoLoadVD
See “NoLoadVD” on page 9.
Disabled Enabled,
Disabled
Figure 10 Advanced Inverter Settings Menu Screen
Table 3
Advanced Inverter Settings Description and Values
a
a.Applies to all CSW models.
Item Description Default Range
LBCO
Hysteresis
See “Low Battery Cut Out
Hysteresis” on page 9.
2.0V 0.5V to 5.0V
LBCO Delay
See “LBCO Delay” on page
9.
10sec 0sec to 600sec
Table 2
Adv Features Description and Values
Item Description Default Range
CSW4024E 00: Inv
Low Batt Cut Out
LBCO Hysteresis
LBCO Delay
Hi Batt Cut Out
Search Watts
Search Delay
Inv Block Start
Inv Block Stop
[21.0V]
[2.0V]
[10sec]
[29.0V]
[50W]
[2sec]
[hh:mm AM]
[hh:mm AM]
CSW4024E 00: Adv
Inverter Settings
Charger Settings
AC Settings
Gen Support
Multi Unit Config
Restore Defaults
Adv Features
[*2.0V] [0.5V] to [5.0V]
[*10sec] [0sec]to [600sec]
For details on older settings, consult the Conext SW Owner’s Guide.