Conext SW 4048-120 Manual Addendum

Documentation Update
14 976-0315-01-01 Rev E
Load Shave Setting
For Load shaving to be effective, all loads must be connected to the inverter. For
large loads, stacked CSW inverters may be required. To help the batteries
supplement the power requirements of the connected load, an additional source
of power (like solar, wind, or hydroelectric) is recommended but not required.
To demonstrate a scenario where load shaving takes effect on the CSW, the
following settings are programmed into the SCP.
Scenario Settings: Load Shave=Enabled
LoadShaveAmps=10A
LoadShaveStart=6:00AM
LoadShaveStop=9:00PM
PLSDelay=Enabled
To use the Load Shaving feature:
1. Enable load shaving.
2. Set the load shaving amps.
3. Set the load shaving start and stop times.
CSW4024E 00: AC Support
AC Supp Mode
AC Supp Volts
Load Shave
Load Shave Amps
[Disabled]
[26.0V]
[Enabled]
[24A]
CSW4024E 00: Adv
Inverter Settings
Charger Settings
AC Settings
AC Support
Multi Unit Config
Restore Defaults
Adv Features
Go to Advanced Settings -> AC Support ->
Load Shave
Press Enter, then select Enabled using the up
and down arrow buttons. Press Enter.
From AC Support -> Load Shave Amps
Press Enter, then select a value of 10 using the up
and down arrow buttons. Press Enter.
CSW4024E 00: AC Support
AC Supp Mode
AC Supp Voltsp
Load Shave
Load Shave Amps
[Enabled]
[Disabled]
[Enabled]
[10A]
From AC Support -> LoadShaveStart
Press Enter, then a time of 9:00 PM using the up and
down arrow buttons. Press Enter.
Press Enter, then a time of 6:00 AM using the up and
down arrow buttons. Press Enter.
From AC Support -> LoadShaveStop
CSW4024E 00: AC Support
LoadShaveStart
LoadShaveStop
AC Supp on Soc
AC Supp Start Soc
[6:00 AM]
[9:00 PM]
[Disabled]
[80%]