Conext SW 4048-120 Manual Addendum

Documentation Update
976-0315-01-01 Rev E 15
4. Enable the grid-interactive delay feature.
In this scenario, load shaving is only entered and exited as programmed within
the time window (from 6 AM to 9 PM).
Additionally, with these scenario settings, the CSW would enter load shaving
within the configured time and also only if the battery has been charged from an
MPPT charge controller in Float (including Absorption) for 2 hours.
CSW4024E 00: Adv Fea
StoreInvState
AcCouple
EnhancedAcSup
PLSDelay
[Disabled]
[Disabled]
[Disabled]
[Enabled]
CSW4024E 00: Adv
Inverter Settings
Charger Settings
AC Settings
AC Support
Multi Unit Config
Restore Defaults
Adv Features
Go back to Advanced Settings
-> Adv Features -> PLSDelay
Press Enter, then select Enabled using the up
and down arrow buttons. Press Enter.
NOTE: In the absence of an MPPT charge controller, charger block stop and
start settings must be set at the same times as the load shaving stop and start
settings. Otherwise, charging may start even during load shaving.