Schneider Electric User Guide
Troubleshooting
4–14 975-0240-01-01
W70 Synchronization
Warning
Manual,
AC input
is not
qualified
1. An AC input voltage
phase is lost or out of the
AC range in the
three-phase.
2. AC input voltage
phases are not
synchronized with Conext
3-phase system.
1. Check the AC voltage
presence of each phase at the
AC input terminals for each
Conext XW+.
2. Inspect the three-phase
wiring to have the correct
phase sequence: XW-Phase-A,
XW-Phase-B, XW-Phase-C with
the same AC input sequence to
each unit.
W94 Remote Power Off Automatic The unit has been turned
off with a Remote Power
Off switch.
No action required. The unit
stops inverting or charging
immediately, and shuts down
after five seconds. If the unit is
configured as a master, it
signals other network devices
to also shut down.
W95 Equalize Abort Manual Equalization terminated
abnormally because of
interrupted AC input.
Wait until AC input (utility grid)
returns to in-tolerance
condition.
W96 Cannot Equalize Manual The selected battery type
should not be equalized.
AC input is not qualified
or the charge setting is
not adequate.
Change battery type if your
batteries should be equalized.
Gel or AGM batteries should
not be equalized.
Check for presence of AC.
Make sure Charge and
Equalize are enabled. Verify
the Conext AGS trigger is set to
Stop Float. If Stop V is
enabled, then the voltage level
should be above the
Eqlz Voltage level.
W97 Battery
temperature
sensor failure
Automatic Battery Temperature
Sensor Shorted
Replace battery temperature
sensor.
W500 Lost network
connection
Automatic Lost network connection Check network cables.
Table 4-3 Warning Messages
Warning
Number
Conext System
Control Panel
Message
Warning
Type Cause Solution
Conext XW+ Owner's Guide NA (975-0240-01-01).book Page 14 Monday, November 27, 2017 10:00 AM