Schneider Electric User Guide

Default Settings and Ranges
975-0240-01-01 B–3
Inverter Settings Menu
Charger Settings Menu
Custom Settings Submenu
Item Default Setting Range Step Size
Low Batt Cut Out
44 V 36–48 V 0.1
LBCO Hysteresis
2 V 0-10 V 0.1
LBCO Delay
10s 0–600s 1
High Batt Cut Out
65 V 58–70 V 0.1
Search Watts
50 W 25–255 W 5
Search Delay
2s 1–25s 1
Item Default Setting Range Step Size
Batt Type
Flooded Flooded, Gel, AGM,
Custom
a
a.When Custom battery selected, two sub-menus appear: Custom Settings and
LithiumIon
n/a
Batt Capacity
440 Ah
0–10000 Ah
b
b.Setting the battery capacity to 0 will reset the charging current to its default val-
ues. Zero Ah battery capacity implies there is no absorption exit current criteria
and absorption only exits when the absorption timer (default 3 hrs, range 1 min-
8 hr) expires.
1
Max Chg Rate
100% 5–100% 1
Charge Cycle
2-Stage 2-Stage, 3-Stage n/a
Default Batt Temp
Warm Cold, Warm, Hot n/a
ReCharge Volts
50 V 40.0–54.0 V 0.1
Absorb Time
180 min 1–480 min 1
Chg Block Start
12:00 AM 12:00 AM–11:59 PM,
00:00–23:59
1
Chg Block Stop
12:00 AM 12:00 AM–11:59 PM,
00:00–23:59
1
Item Default Setting Range Step Size
Eqlz Support
Enabled Enabled, Disabled n/a
Eqlz Voltage
64.0 V 54.0–64.0 V 0.1
Bulk Voltage
a
57.6 V
56.8 V (Gel)
57.2 V (AGM)
54.2–64.0 V 0.1
Absorb Voltage
a
57.6 V
56.8 V (Gel)
57.2 V (AGM)
40.0–64.0 V 0.1
Float Voltage
a
54.0 V
55.2 V (Gel)
53.6 V (AGM)
50.0–64.0 V 0.1
Conext XW+ Owner's Guide NA (975-0240-01-01).book Page 3 Monday, November 27, 2017 10:00 AM