Schneider Electric User Guide
Default Settings
B–4 975-0240-01-01
LithiumIon Submenu
AC Menu
Batt Temp Comp
a
108 mV/C (Flooded,
Gel)
84 mV/C (AGM)
0–180 mV/C 1
a.Custom battery default settings are based on the Flooded battery default set-
tings. The Gel and AGM default settings are provided here for reference only.
Item Default Setting Range Step Size
Control EXT_BMS EXT_BMS, 3stage,
2stageNoFloat
n/a
Bulk Voltage 57.0 V 40.0–64.0 V 0.1
Max Bulk Current 140 A 10-140 A 1
Abs Voltage 58.0 V 40.0–65.0 V 0.1
Max Abs Current 140 A 10-140 A 1
Float Voltage 53.6 V 40.0–64.0 V 0.1
Max Float Current 140 A 1-140 A 1
DisChglmax 150% 20-500% 1
DisChglmax Timer 10 sec 0-300 sec 1
Item
Default Setting Range
Step Size
120
VAC
240
VAC
120
VAC
240
VAC
AC Priority
AC1 AC1, AC2 n/a
AC1 Breaker
60 A 3–60 A 1
AC1 Lo Volt
106 V 212 V 60–115 V 156–230 V 1
AC1 Hi Volt
135 V 270 V 125–144 V 250–288 V 1
AC1 Lo Freq
55 Hz 44–59 Hz 1
AC1 Hi Freq
65 Hz 44–70 Hz 1
AC2 Breaker
60 A 3–60 A 1
AC2 Lo Volt
80 V 160 V 60–115 V 120–230 V 1
AC2 Hi Volt
138 V 276 V 125–144 V 250–288 V 1
AC2 Lo Freq
54 Hz 44–58 Hz 1
AC2 Hi Freq
65 Hz 44–70 Hz 1
Item Default Setting Range Step Size
Conext XW+ Owner's Guide NA (975-0240-01-01).book Page 4 Monday, November 27, 2017 10:00 AM