Schneider Electric User Guide

Default Settings and Ranges
975-0240-01-01 B–5
Grid Support Menu
Gen Support Menu
Aux Menu
Item
Default Range Step Size
Grid Supp Volts
53.0 V
a
a.The setting for Grid Supp Volts must be greater or equal to LBCO+2 V. For example, if
LBCO is 44 V then the minimum Grid Supp Volts is 46 V.
42.0–70.0 V
0.1
Sell
Disabled Disabled, Enabled n/a
Max Sell Amps
b
b.This setting is restricted to the selected external AC1 breaker size.
27 A (XW+ 6848),
20 A (XW+ 5548)
0–27 A (XW+ 6848),
0–20 A (XW+ 5548)
1
Load Shave
Disabled Disabled, Enabled n/a
Load Shave Amps
48 A 0–48 A 1
Load Shave Start
c
c.When Load Shaving is enabled, if Load Shave Start and Load Shave Stop are set to the
same time, the Conext load shaves continuously.
12:00 AM 12:00 AM–11:59 PM,
00:00–23:59
1
Load Shave Stop
12:00 AM 12:00 AM–11:59 PM,
00:00–23:59
1
Sell Block Start
12:00 AM 12:00 AM–11:59 PM,
00:00–23:59
1
Sell Block Stop
12:00 AM 12:00 AM–11:59 PM,
00:00–23:59
1
Setting Default Range Step Size
GenSupp Mode
Disabled Enabled, Disabled n/a
GenSupp Amps
48 A 0–48 A 1
Item
Default Range
Step Size
Manual Aux
ManualOff ManualOn, ManualOff,
Automatic
n/a
Active Lvl
ActiveHigh ActiveHigh, ActiveLow n/a
Trig Src
a
LowBattV LowBattV, HighBattV,
LowBattTemp,
HighBattTemp, Fault
n/a
Trigger Level—
LowBattV
b
46.0 VDC 40.0–58.0 VDC
0.1
Clear Level—
LowBattV
48.0 VDC 40.0–58.0 VDC
0.1
Trigger Level—
HighBattV
56.0 VDC 48.0–64.0 VDC
0.1
Clear Level—
HighBattV
52.0 VDC 48.0–64.0 VDC
0.1
Conext XW+ Owner's Guide NA (975-0240-01-01).book Page 5 Monday, November 27, 2017 10:00 AM