Schneider Electric User Guide

Default Settings
B–6 975-0240-01-01
Connections Menu
Advanced Features Menu
For an explanation of these features, see “Using the Advanced Features” on
page 3–49.
Trigger Le vel
HighBattTemp
45.0°C
30.0–60.0°C
1
Clear Level—
HighBattTemp
35.0°C 30.0–60.0°C 1
Trigger Le vel
LowBattTemp
0.0°C -30.0–10.0°C 1
Clear Level—
LowBattTemp
5.0°C -30.0–10.0°C 1
Trigger Delay
1s 0–600s 1
Clear Delay
1s 0–600s 1
a.The Trigger Src setting (and the settings below Trigger Src) appear only if
Manual Aux setting has been set to Automatic.
b.Trigger Level, Trigger Delay, Clear Level and Clear Delay do not appear if
Trigger Src is set to Fault.
Item Default Range Step Size
DCConn
HouseBatt1 HouseBatt1–6 n/a
ACOut
ACLoad1 ACLoad1–10 n/a
AC1
Grid 1 None, Grid1–10,
Gen1–10
n/a
AC2
Gen 1 None, Grid1–10,
Gen1–10
n/a
Item Default Range Step Size
RPO
Disabled Enabled, Disabled n/a
Power Save
Disabled Enabled, Disabled n/a
Sell Dly 40s
Disabled Enabled, Disabled n/a
AC_Coupling
Enabled Enabled, Disabled n/a
Batt_Balance
Disabled Enabled, Disabled n/a
EXT_CONTACT
Enabled Enabled, Disabled n/a
EXT_LOAD_SW
Disabled Enabled, Disabled n/a
PLS DLY 2h
Disabled Enabled, Disabled n/a
TOV_DISCNCT
a
a.Hawaii HECO TOV requirement
Enabled Enabled, Disabled n/a
Item
Default Range
Step Size
Conext XW+ Owner's Guide NA (975-0240-01-01).book Page 6 Monday, November 27, 2017 10:00 AM