Schneider Electric User Guide

Monitoring Operation
2–2 975-0240-01-01
Monitoring Operation with the Inverter Information Panel
The inverter information panel on each Conext XW+ monitors a single Conext
XW+. The Conext XW+ information panel displays basic information and
performs start up, shut down, equalization and standby functions. LEDs on the
information panel indicate AC input status, Conext XW+ status, battery condition,
and charging and equalization status. The Conext XW+ LEDs and three-
character display screen indicate warning and event conditions.
Monitoring AC Input Status
Grid (AC1) The green Grid (AC1) LED indicates the presence and status of the
AC source connected to the AC1 input.
Gen (AC2) The green Gen (AC2) LED indicates the presence and status of a
generator or other auxiliary AC source on the AC2 input.
Figure 2-1 Inverter Information Panel
Symbol LED On LED Flashing LED Off
AC input is present and
qualified. The Conext
XW+ is ready to charge
batteries, pass AC
through to the loads, or
interact with the grid.
AC input is
present and is
being qualified.
The Conext XW+ is not
connected to the grid.
AC input is not
present, or AC input is
present but not within
qualifying range.
Symbol LED On LED Flashing LED Off
The AC source is present
and AC input is qualified.
The Conext XW+ is ready
to charge batteries and
pass power through to
the loads.
AC input is
present and is
being qualified.
AC input is not
present, or AC input is
present but not within
qualifying range.
Conext XW+ Owner's Guide NA (975-0240-01-01).book Page 2 Monday, November 27, 2017 10:00 AM