Inverter Settings Menu
975-0240-01-01 3–9
Using the Low Battery Cut Out and LBCO Delay Settings
The Low Batt Cut Out setting is the lowest battery voltage level acceptable for
use by the inverter. When the batteries discharge to the Low Batt Cut Out
setting, and are held at or below this level for the LBCO Delay time, the inverter
output shuts down and connects any available AC source (AC1 or AC2) to the
charger to bring the battery level back above the Low Batt Cut Out setting. After
shutdown, the inverter does not support loads on AC OUT, and AC loads must be
powered by either a generator (AC2) or grid power (AC1). If the battery voltage
stays below the LBCO voltage for more than 24 hours, the Conext XW+ shuts
down.
If using the Conext Automatic Generator Start system, it is recommended to
set the Conext AGS voltage trigger setting higher than the Conext XW+ Low
Batt Cut Out voltage.
Although not recommended, if using the Conext Automatic Generator Start
system with the start trigger set to the same voltage as the LBCO voltage, do
not set the LBCO Delay for less than the amount of time it takes the generator
to start and connect.
Otherwise – in both of the scenarios above – inverter output turns off before the
generator automatically starts, causing the battery voltage to recover slightly.
This may then stop the Conext AGS from starting the generator or result in the
Conext XW+ cycling on and off multiple times before the generator automatically
starts.
Using Search Mode
Why use Search
mode?
Search mode allows the inverter to selectively power only items that draw more
than a certain amount of power, which can result in energy savings. The Conext
XW+ has a no-load power draw of about 28 watts. Enabling search mode
reduces this power draw to less than 8 watts. Search mode operates differently in
single-unit and multi-unit installations.
WARNING
ADVANCED CONFIGURATION HAZARD
Advanced menu settings should be used by qualified personnel only.
Three phase operation should be configured by qualified personnel only.
Consult with the local utility before enabling Conext XW+ sell mode or grid
support functions.
Do not change these settings unless you are under the supervision and
direction of qualified personnel.
Failure to follow these instructions can result in death or serious injury.