Schneider Electric User Guide
Charger Settings Menu
975-0240-01-01 3–17
Figure 3-5 Two-Stage Charging Cycle
Time
Time
Absorption Voltage
Max Absorb Time - Dflt 3 hrs
(adjustable 1 min - 8 hrs )
Boost
Timer
1hr fixed
2-Stage Charge
Custom Charge
Absorption Stage
Bulk Stage
(Boost Stage)
Recharge
Voltage
Battery
Voltage
Battery
Current
Max Charge
Rate
Return to
Bulk Stage
Absorption Exit Current
Threshold = 2% of
programmed AH capacity
Conext XW+ Owner's Guide NA (975-0240-01-01).book Page 17 Monday, November 27, 2017 10:00 AM