Schneider Electric User Guide

Charger Settings Menu
975-0240-01-01 3–23
3Stage Used for 3-Stage Lithium Ion charging. Allows for Bulk Voltage, Max Bulk
Current, Absorb Voltage, Max Absorb Current, Float Voltage, Max Float
Current, DisChglmax, and DisChglmax Timer settings (in shaded rows).
Bulk Voltage Appears only when the Control is set to 2StageNoFloat and 3Stage. Sets the
bulk voltage limit for a lithium ion battery when in Bulk Charge Mode.
Max Bulk Current Appears only when the Control is set to 2StageNoFloat and 3Stage.
Sets the bulk current for a lithium ion battery type. This configures the current
limit when the Conext XW+ is in Bulk Charge Mode. However, between the
maximum charge current (Max Chg Rate × maximum DC output current) [see
“Charger Settings Menu” on page 3–11] and the value set here, the Conext
XW+ charger will charge at the lesser of these two values.
Absorb Voltage Appears only when the Control is set to 3Stage. Sets the absorb voltage limit
for a lithium ion battery when in Absorption Charge Mode.
Max Abs Current Appears only when the Control is set to 3Stage.
Sets the absorb current for a lithium ion battery type. This configures the
current limit when the Conext XW+ is in Absorption Charge Mode. However,
between the maximum charge current (Max Chg Rate × maximum DC output
current) [see “Charger Settings Menu” on page 3–11] and the value set here,
the Conext XW+ charger will charge at the lesser of these two values.
Float Voltage Appears only when the Control is set to 3Stage. Sets the float voltage limit for a
lithium ion battery when in Float Charge Mode.
Max Float Current Appears only when the Control is set to 3Stage.
Sets the float current for a lithium ion battery type. This configures the current
limit when the Conext XW+ is in Float Charge Mode. However, between the
maximum charge current (Max Chg Rate × maximum DC output current) [see
“Charger Settings Menu” on page 3–11] and the value set here, the Conext
XW+ charger will charge at the lesser of these two values.
DisChglmax Each Lithium Ion battery has an internal contactor and over load protection
which is based on maximum current. If exceeded, the contactor may open,
resulting in complete isolation of the battery pack, thus removing power to the
Conext XW+. In this case the Xanbus communication as well as devices
powered from the Conext XW+ could become unusable. When the Conext XW+
current draw exceeds the set value for a period defined in DisChglmax Timer,
the Conext XW+ disables INV output. Appears only when the Control is set to
2StageNoFloat and 3Stage.
DisChglmax Timer Allows the Conext XW+ current in Invert mode to exceed the DisChglmax limit
for inrush periods to startup loads such as pumps/motors. When the timer
expires, the Conext XW+ disables INV output. Appears only when the Control
is set to 2StageNoFloat and 3Stage.
a. Custom Settings is displayed when Batt Type is set to Custom.
b.The Eqlz Voltage setting is displayed when Eqlz Support is set to Enabled.
c. LithiumIon is displayed when Batt Type is set to LithiumIon.
Table 3-4 Custom Battery Settings Menu
Item Description
Conext XW+ Owner's Guide NA (975-0240-01-01).book Page 23 Monday, November 27, 2017 10:00 AM