Schneider Electric User Guide
Configuration
3–36 975-0240-01-01
For default settings, see “Gen Support Menu” on page B–5.
AGS Setting in a
Multi-Cluster
System
The AGS setting Load enables and disables the Load Start and Load Stop
triggers. To prevent the generator from nuisance cycling when the multi-cluster
XW+ units are installed with an external contactor (that is, the generator starts
and stops in a loop) set Load = Disabled under the Cfg Trigger menu.
Note: When GenSupp Mode is enabled and actively operating, the Conext XW+
compensates for active power as a reference for controlling the total current as
specified in the GenSupp Amps setting. However, there is also reactive power that
is not compensated for by the Conext XW+. For example, if GenSupp Amps is set
to 48A, the inverter will only start to assist the generator at a current level which
would measure approximately 49A which is 1A higher than the GenSupp Amps
value.