Schneider Electric User Guide

Auxiliary Output Settings
975-0240-01-01 3–37
Auxiliary Output Settings
The Aux menu allows you to enable and set the auxiliary output. The auxiliary
output provides 12 volts DC at 250 milliamps to power a relay, indicator light, or
alarm.
For default settings, see “Aux Menu” on page B–5.
WARNING
ADVANCED CONFIGURATION HAZARD
Advanced menu settings should be used by qualified personnel only.
Three phase operation should be configured by qualified personnel only.
Consult with the local utility before enabling Conext XW+ sell mode or grid
support functions.
Do not change these settings unless you are under the supervision and
direction of qualified personnel.
Failure to follow these instructions can result in death or serious injury.
Note: Changing Trigger Level resets the auxiliary output. If an auxiliary output
trigger is active, changing the trigger level will clear the trigger.
Table 3 -8 Aux Menu Values
Setting Description
Manual Aux Sets the state of the auxiliary output. ManualOn or ManualOff
allow manual control of the auxiliary output. When set to
Automatic, a trigger source can then be selected.
Active Lvl Sets the mode (polarity) of the auxiliary output. When triggered,
the output can be active high (12 V output turns on) or active
low (output is high until the trigger turns it off).
Trigger Src Selects the desired condition (trigger source) to activate the
auxiliary output. The trigger source options are LowBattV,
HighBattV, LowBattTemp, HighBattTemp, TOD and Fault.
Trigger
Level
Sets the voltage or temperature level (depending on the
selected trigger source) at which the auxiliary output is
activated. If the selected Trigger Src is a battery voltage, the
range also varies according to the nominal battery voltage of
your system.
Trigger
Delay
Sets a delay period between when the trigger occurs and when
the auxiliary output is activated.
Clear Level
Sets the voltage or temperature level (depending on the
selected trigger source) at which the auxiliary output becomes
inactive.
Clear Delay Sets a delay period between when the Clear Level setting
occurs and when the auxiliary output becomes inactive.
Conext XW+ Owner's Guide NA (975-0240-01-01).book Page 37 Monday, November 27, 2017 10:00 AM