Schneider Electric User Guide

Configuration
3–40 975-0240-01-01
Table 3-9 Multi-Unit Config Menu
Item Description Default Range
Dev Name Allows customization of the default device name.
This setting is optional and does not affect operation.
See “Setting the Device Name” on page 3–41.
n/a n/a
Dev Number Allows setting of a unique unit number in a multiple-unit
system. See “Setting the Device Number” on page 3–42.
00 00–31
Inverter
Mode
For a split-phase system: For a multi-unit system to
operate, one Conext XW+ must be configured to
SplitPhMaster and the rest as SplitPhSlave, otherwise
a system-wide fault is asserted.
SplitPhMaster
For single-
phase, three-
wire models:
SplitPhMaster,
SplitPhSlave
For a single-phase system:
For a multi-unit system to
operate, one Conext XW+ must be configured to
1PhMaster
and the rest as
1PhSlave
, otherwise a system-
wide fault is asserted.
Before setting up a single-phase system, perform the steps
in “Converting 120 V/240 V Split-Phase to 120 V Single-
Phase” in the
Conext XW+ Inverter/Charger Installation
Guide.
1PhMaster
SplitPhMaster,
SplitPhSlave
For a three-phase system: See “Three-Phase Configuration” on page 3–43.
Connections Select to display the Connections menu.
See “Connections Menu” on page 3–45.
n/a n/a
Conext XW+ Owner's Guide NA (975-0240-01-01).book Page 40 Monday, November 27, 2017 10:00 AM