Setting the Device Number
When several devices of the same type are installed in the Xanbus network,
setting the device number is required to give a Xanbus-enabled device a unique
identity. When each identical device has a unique number, the Conext SCP can
correctly identify and display status information for each device. A device
number consists of two digits ranging from 00 (default) to 31.
If only one of each type of device is installed in the networked power system, a
device number is not needed. However, setting the device number to a value
other than 00 is recommended in case you need to use the Restore Defaults
command. This command resets the device number to 00. After performing the
command, checking that the device number has returned to 00 indicates that the
command was successfully completed.
To set the Conext XW+ device number:
1. On the Conext XW+ Setup menu, select Advanced Settings.
If Basic Settings appears instead of Advanced Settings on the Setup
menu, display Advanced Settings by pressing Enter + Up arrow + Down
arrow simultaneously.
On the Advanced Settings menu, select Multi-Unit Config and press
Enter.
2. On the Multi-Unit Config menu, select Dev Number. See Figure 3-10.
3. Press Enter to highlight the instance number.
4. Use the up and down arrow buttons to adjust the two-digit identifier number.
5. Press Enter.
Figure 3-10 Setting a Device Number
XW+ 6848 01:Multi
Dev Number
[XW1]
[01]
[SplitPhSlave]